Add to Cart
The outdoor UPS system has good protection function: such as heat insulation,dustproof, damp proof, waterproof etc.
● Double conversion on line technology, which enables the UPS to provide apure sine wave voltage, with constant frequency, constant voltage, low noiseand no interruption, no matter the utility power fluctuation. It protects theuser’s equipment ideally all the time.
● The system has two doors, you can open the front or back door to operate thesystem. There are four layers inside the system, the first layer is used to holdbatteries ; The second floor installation lightning protection device, powerdistribution equipment etc;the third layer is used for install the UPS module,lightning protection devices, maintenance switch etc , the four layer is usedfor install fan module.
Model | 1KVA | 2KVA | 3KVA | 6KVA | 10KVA |
Range voltage | 220/230/240VAC | ||||
Frequency | 50Hz/62Hz | ||||
Input | |||||
Voltage range | 115~295VAC(±3VAC) | 176~297VAC(±3VAC) | |||
Frequency Range | 50Hz (46~54 Hz) ; 60Hz (56~64 Hz) | ||||
Soft Start | 0~100% 5sec | ||||
Power factor | 0.98 | ||||
Output | |||||
Voltage Precision | 220/230/240VAC(1±2%)AC | ||||
Frequency Precision | 50Hz/62Hz±0.05Hz | ||||
Power factor | 0.7/0.8(optional) standard 0.7 | ||||
Wave Distortion | Linear load<3% Non-linear load<6% | ||||
Overload capability | Overload(110~150%)for 30 seconds,then automatically transfer to bypass.When load is normal,it can automatically transfer to normal mode | ||||
Crest Factor | 3:01 | ||||
Transfer time | 0ms (AC to DC) | ||||
battery | 36VDC | 72VDC | 96VDC | 240VDC | 240VDC |
Charging current | 4A/8A(optional) | 4A/8A(optional) | 4A/8A(optional) | 4.2A | 4.2A |
Internal Battery Caoacity | (38/65/80/100AH) optional | ||||
Panel display | |||||
LED | Load level/Battery level ,Battery indicator,Utility power,Inverter ,Bypass,Overload ,Fault | ||||
Communications | |||||
Communications interface | RS232 SNMP card(optional) | ||||
Work Environment | |||||
Temperature | -40~55ºC | ||||
Humidity | 0~95%(Non-condensing | ||||
Storage Temperature | -25ºC~55ºC | ||||
Elevation | <1500m | ||||
Physical Characteristics | |||||
Weight(KG)N.W | 85 | 125 | 125 | 150 | 150 |
Dimensions:(WxDxH)mm | 613*640*954 | 650*753*1227 | 650*753*1227 | 940*940*1770 | 940*940*17 |