Shenzhen Zhongguanda Technology Co., Ltd.

Customer first, unity and mutual assistance, learning and innovation, open sharing

Manufacturer from China
Site Member
5 Years
Home / Products / Modular Online UPS /

Low Frequency 80KVA Modular UPS System 3 Phases 380V 400V 415V Power

Contact Now
Shenzhen Zhongguanda Technology Co., Ltd.
City:shenzhen
Country/Region:china
Contact Person:MrMark
Contact Now

Low Frequency 80KVA Modular UPS System 3 Phases 380V 400V 415V Power

Ask Latest Price
Video Channel
Brand Name :ZGD
Model Number :ZGD-M80
Place of Origin :Guangdong, China
MOQ :1
Price :$500.00/Pieces 1-9 Pieces
Payment Terms :T/T, Western Union
Supply Ability :10000 Piece/Pieces per Month
Delivery Time :10-15 work days
Packaging Details :wooden box
Warranty :1year
Phase :Three Phase
Protection :Short Circuit
Weight :286kg
Type :On-line
Application :INSTRUMENTATION
Product name :Low Frequency Online UPS
Capacity :80KVA
Battery Type :Lead Acid Battery
Wave Form :Pure Sine Wave
Color :Black
Certificate :CE
Display :LCD
Input voltage :305VAC - 460VAC
Output :380VAC 3+N+PE 50HZ
Appplication :Military
Port :Shenzhen
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Low Frequency 80KVA Modular UPS System 3 Phases 380V 400V 415V Power

80KVA Modular Online UPS Pure Sine Wave Data Center System Power 3 Phases UPS 380V/400V/415V
Main Features
High efficiency online double conversion technology
High scalability
Unity output power factor
Modular design lowers MTTR
N+1 or N+X parallel redundancy for power guarantee
Ease of installation and maintenance
Flexible battery configuration adapts different applications
Adjustable charging current
High overload capability
Graphic 5.7” LCD design for easy management
Model ZGD-M80
Phase 3-phase in / 3-phase out
Capacity 80KW or 120KW
One power module capacity 20KVA/20KW
Battery type External battery
MAX.power module NO. 4
MAX.battery set NO. /
INPUT
Nominal Voltage 3x380VAC/400VAC/415VAC(3Ph+N)
Voltage range 305-478VAC at 100%load; 208-304VAC at<70% load
Frequency range 40-70Hz
Power factor >0.99 @100% load, > 0.98 @ 50%load
Harmonic distortion
(THDi)
<3% @ 100% load
OUTPUT
Nominal Voltage 3x380VAC/400VAC/415VAC(3Ph+N)
Voltage regulation
steady statu
≤±1% typical (balanceload), ≤±2% typical (unbalanceload)
Nominal range 50/60Hz
Frequency range 46- 54Hz or 56 - 64Hz
THDu THD<1%( linear load),THD<5.5%(non- linear load)
Overload Capacity 1 hour for 110%,10 mins for 125%,1min for 150%,200ms for >150%
Total Harmonic Distortion ≤2% (linear load); ≤4% (non-linear load)
Efficiency Up to 94.5%
BATTERY / CHARGER
Nominal Voltage ±216VDC(12V x 36pcs)
Max.Voltage ±240VDC(12V x 40pcs)
Min. Voltage ±192VDC(12V x 32pcs)
Floating current voltage 2.25V /Cell
Boost current voltage 2.35V / Cell
Temperature compensation yes
Max.charging current 8A 8A for 30kw power module 6A 8A
Per power module 6A for 20kw power module
PHYSICAL
Cabinet dimension(mm) 1100x600x1475 1100x600x2010 1100x600x1475 1100x600x1475 1100x600x2010
Net weight(KGS) 675 932 335 or 333 437.5 or 434.5 611 549
549
Operation temperature 0-40℃
Related humidity 0-95%(non-condensing)
Altitude
IP class IP20
MANAGEMENT
Smart RS232/USB Support Windows 2000/2003/XP/Vista/2008/7/8,Linux and MAC
Opionat SNMP car Power management from SNMP manager and Web browser
STANDARDS
Safety IEC/EN 60950-1;IEC/EN 62040-1
EMC IEC/EN 62040-2 CATEGORY C3