Add to Cart
High Frequency Online Rack Mount 6KVA ~ 10KVA Pure Sine Wave Ups Power Without Battery
Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208 VAC.
When using batteries from 16-19, the unit will de-rate according to the formula: P=Prating x N/20
If the UPS is installed or used in a place where the altitude is above than 1000m,
the output must be derated one percent per 100m.
Product specifications are subject to change without further notice.
Model | ZGD 6K (L) RT | ||||
PHASE | 1 phase in/ 1 phase out | ||||
CAPACITY | 6000 VA/6000 W | ||||
INPUT | |||||
Nominal Voltage | 208/220/230/240 VAC | ||||
Voltage Range | 110-300 VAC @ 0~60% load; 140-300 VAC @ 60~80 % load; 176-300 VAC @ 80~100 % load | ||||
Frequency Range | 46 ~54 Hz or 56~64 Hz | ||||
Phase | |||||
Power Factor | ≧ 0.99 @ 100% Load | ||||
THDi | ≦ 4% @100% load; <6% @ 50% load | ||||
OUTPUT | |||||
Output Voltage | 208*/220/230/240 VAC | ||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||
Frequency Range (Synchronized Range) | 46~54 Hz @ 50 Hz or 56~64 Hz @ 60 Hz | ||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||
Current Crest Ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≦1.5% THD (Linear Load), ≦ 7 % THD (Non-linear Load) | ||||
Transfer Time | AC Mode to Batt. Mode | zero | |||
Inverter to Bypass | zero | ||||
Waveform (Batt. Mode) | Pure Sinewave | ||||
Overload | AC Mode | 100%~110%: 10 min; 110%~130%: 1 min; >130%: 1 sec | |||
Battery Mode | 100%~110%: 30 sec; 110%~130%: 10 sec; >130%: 1 sec | ||||
BATTERY | |||||
Standard Model | Battery Type | 12V/7 Ah | |||
Numbers | 16 | ||||
Typical Recharge Time | 9 hours recover to 90% capacity | ||||
Charging Current (Max.) | 1.0A | ||||
Charging Voltage | 218.4 VDC ±1% | ||||
Long-run Model | Battery Type | Depending on applications | |||
Numbers | 16-20** | ||||
Charging Current (Max.) | 4.0A | ||||
Charging Voltage | (13.65 VDC x battery number) ± 1% | ||||
INDICATORS | |||||
LCD Panel | UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions | ||||
PHYSICAL | |||||
Standard Model | Dimension, DxWxH (mm) | UPS Unit: 600x438x88 [2U]; Battery Pack: 695x438x88[2U] | |||
Net Weight (kgs) | UPS Unit: 15; Battery Pack: 48 | ||||
Long-run Model | Dimension, DxWxH (mm) | 600x438x88 [2U] | |||
Net Weight (kgs) | 15 | ||||
ENVIRONMENT | |||||
Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) | ||||
Noise Level | Less than 55dB@1Meter | ||||
MANAGEMENT | |||||
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser |